Products
Your present location:Products >> In rack cooling >> Chilled water in rack cooling >> Chilled water in rack cooling
  • name: Chilled water in rack cooling
  • Views : 44

Chilled water unit (RUC__H)

CW series the cooling is provided by external chillers and dry coolers, to better use the freecooling system.

■ Cooling capacity: 14-70kW

■ New generation EC brushless fans

■ 2 way or 3 way(optional) modulating valves

■ G4 filter and filter blocking switch

■ High sensible heat ratio(SHR≥0.90)

■ Optimal integration with Renovo Freecooling chillers

■ Adopt hot plug fan(optional) as easy maintenance

■ Easy handling due to integrated wheels

 

Chilled water RTR unit

 

Model

RUC__H

0250

0350

0500

Chilled water inlet/outlet temp.

℃/℃

7/12

10/15

12/17

7/12

10/15

12/17

7/12

10/15

12/17

Total/Sensible Cooling Capacity

40℃/20%RH

kW

34.6

31.2

28.9

48.8

44.0

40.7

71.0

63.8

59.3

37℃/24%RH

kW

31.1

27.7

25.5

43.8

39.0

35.8

63.8

56.8

52.2

35℃/27%RH

kW

28.8

25.4

23.2

40.5

35.8

32.6

59.0

52.0

47.5

32℃/31%RH

kW

25.4

22.0

19.7

35.7

30.9

27.7

52.0

45.0

40.3

30℃/35%RH

kW

23.1

19.6

17.4

32.5

27.7

24.4

47.3

40.2

35.5

27℃/42%RH

kW

19.6

16.2

13.9

27.5

22.7

19.5

40.0

33.0

28.3

DIMENSIONS & WEIGHT

Depth

mm

600

600

600

Width

mm

1200

1200

1200

Height

mm

2000

2000

2000

Weight

kg

195

258

270

CENTRIFUGAL FANS(EC)

Number of Fans

 

7

3

3

Air Flow Volume

m3/h

4200

8500

10000

ELECTRIC HEATER(option)

kW

12

12

12

ELECTRODED HUMIDIFIER(option)

kg/h

8

8

8

Optional function: